Any building's electrical system is intended to serve the needs of the users of the building in a safe manner. However, we must work within constraints such as for our geography, regulations, best practices, and most importantly, the system we employ below:
This page provides a "living document" of the Omni Commons electrical system. It is not necessarily completely accurate, though it strives to be, and is always important to get updated! Also see our [[power usage]], [[floorplans]], [[Media:Panel Diagram.pdf|old breaker diagram]], and [[cancelled panels]].


==System==
3 of these panels are Federal Pacific Electric and need to be replaced ASAP: [[#Panel A|A]], [[#Panel AB|AB]], [[#Panel BA|BA]]


* Label the main electrical panel as '''"main"'''
* '''[[#Main Panel|Main Panel]]''' (in ANV office, room E of rear [48th St] exit)
* Label the direct sub-panels of the main panel with a branch letter, e.g. "A", "B".
** '''[[#Panel A|Panel A]]''' (adjacent to main in ANV office)
* Label each sub-panel that is connected to a first-tier sub-panel of the main panel.
*** '''[[#Panel AB|Panel AB]]''' (in basement next to N staircase)
** '''"level number"''' + '''"origin panel letter"''' + '''"breaker number"'''
*** '''[[#Panel AD|Panel AD]]''' (located upstage left in N corner of W wall of ballroom)
*** e.g. '''"1A2"''' for the first-layer sub-panel from the '''2nd''' breaker on panel '''"A"'''
*** '''[[#Panel AE|Panel AE]]''' (located in storage room S of stage in N corner of W wall of ballroom)
*** e.g. '''"2A3"''' for the second-layer sub-panel from the '''3rd''' breaker on panel '''"1A"''' aka '''"1A2"'''
** '''[[#Panel B|Panel B]]''' (in Crow's Nest above stage in ballroom)
* For each circuit, label each outlet, switch, and load with:
*** '''[[#Panel BA|Panel BA]]''' (in rear ballroom balcony near S wall)
** the appropriate sub-panel name
***** '''[[#Panel BAAA|Panel BAAA]]''' (behind Entrance Hall counter on S wall)
*** e.g. All the outlets in one room that are on the same circuit may be named '''"3C4"''' meaning the cruit is on breaker '''4''' on panel '''3C''', on branch '''C''' from the '''main''' panel.
** '''[[#Panel C|Panel C]]''' (in Disco Room at base of ladder to DJ booth)
** the draw on the curcuit
** '''[[#Panel D|Panel D]]''' (in ANV office on E wall shared with Entrance Hall)
*** e.g. '''20 amps'''
* '''CCL Panel''' - (Located next to door into CCL / sudo room area) - Apparently not yet documented here?
__NOTOC__


==Protocol==
===Main Panel===
[[File:Panel-main.jpg|right|thumb|Omni's main electrical panel]]
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
|rowspan="2"| [[#Panel B|Panel B]] & [[#Panel D|Panel D]] 200amps
| 1 || 2
|rowspan="2"|
|-
| 3 || 4
|-
|rowspan="2"| [[#Panel A|Panel A]] 200amps
| 5 || 6
|rowspan="2"|
|-
| 7 || 8
|-
|rowspan="2"| X
| 9 || 10
|rowspan="2"| [[#Panel C|Panel C]] 100amps
|-
| 11 || 12
|-
|rowspan="2"| Storage #5 / Trash Room
| 13 || 14 || n/a
|-
| 15 || 16 || n/a
|-
| Storage #5 / Trash Room || 17 || 18 || n/a
|-
|rowspan="2"| Counter Culture Labs<br/>(CCL) Closet
| 19 || 20 || n/a
|-
| 21 || 22 || n/a
|-
| n/a || 23 || 24 || n/a
|} <br clear=all>


* We are especially (not exclusively) updating our electrical system documentation on a room-by-room basis.
===Panel A===
* As we do audits and work on individual rooms, you should '''only''' use the system described above to map the electrical system as it is discovered.  
[[File:Panel-a.jpg|right|thumb|Panel A]]
* All other systems will be overridden.
[[File:Panel-A-2021-04-29.jpeg|right|thumb|Panel A open]]
* You can print the worksheet and building floorplan below in order to document the labeling you make on the actual outlets, panels, etc:
 
** After filling out the worksheet and building floorplan, deliver it to the [[Building Construction and Maintenance Working Group|Building Working Group]].
'''''This panel is Federal Electric and needs to be replaced ASAP.'''''
 
200amps
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| || 1 || 21
|rowspan="2"| [[#Panel AE|Panel AE]]
|-
| || 2 || 22
|-
|rowspan="2"| [[#Panel AB|Panel AB]]
| 3 || 23 ||
|-
| 4 || 24 ||
|-
|rowspan="4"| [[#Panel AC|Panel AC]] (breaker is removed until kitchen renovated)
| 5 || 25
|rowspan="4"| [[#Panel AD|Panel AD]]
|-
| 6 || 26
|-
| 7 || 27
|-
| 8 || 28
|-
| || 9 || 29 || &nbsp;
|-
| Upstairs (cafe mezzanine) kitchen light /<br/> Upstairs (cafe mezzanine) bathroom lights /<br/> Exit Sign at top of W cafe mezzanine staircase || 10 || 30 || Sudo Room outlets<br/>on South Wall
|-
| Outlets along north wall of entrance hall
| 11 || 31 ||
|-
| Hood over oven in upstairs<br/> kitchenette (cafe mezzanine) /<br/> W Wall Kitchenette Outlet (R of sink) /<br/> W wall kichenette outlet (Above oven in alcove) || 12 || 32 ||
|-
| CCL storage rooms lights || 13 || 33 ||
|-
|  || 14 || 34 ||
|-
| switch on wall of disco room || 15 || 35 ||
|-
|  || 16 || 36 || X
|-
| Right switch disco room fans || 17 || 37 || Blue Classroom S wall outlets
|-
| 2 TIL Office Lights (upstairs) /<br/> Front Door Exit Sign /<br/>Two Lights on Beam at entrance || 18 || 38 ||
|-
| Light fixture and outlets in <br/>Blue Classroom alcove on N wall || 19 || 39 ||
|-
| Upstairs kitchenette (cafe mezzanine) S wall outlets /<br/> W Wall Kitchenette Outlet (L of sink) /<br/> N wall kitchenette outlets (at entrance) /<br/> Outlets under bar on S Wall of Disco Room <br/>near S Wal of Kitchenette || 20 || 40 ||
|} <br clear=all>
 
===Panel AB===
[[File:Panel-ab.jpg|right|thumb|Panel AB]]
 
'''''This panel is Federal Electric and needs to be replaced ASAP.'''''
 
In 2019 we added another circuit to this box to power lights & outlets in the secure storage closet above it. In the confusion, something may have been switched around. Liblens briefly lost power. Needs to be re-assessed and re-labeled.<br>
<i>"quotes" are from [[Media:Panel Diagram.pdf|old breaker diagram]] re: "DOWNSTAIRS DINING AREA PANEL"</i>
 
7/8 is one breaker, see image.
 
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| 20A basement furnace? "Blank"
| 8 || 16
| 15A "Blank" (nothing connected)
|-
| "Dining Room Furnace"
| 7 || 15
| 15A Liberated Lens, other small basement rooms & adjacent outlets.
|-
| 15A pantry & "Kitchen Lights"
| 6 || 14
| 15A
|-
| 20A
| 5 || 13
| 15A large basement meeting room - most outlets except on south wall "Receptacle"
|-
| 20A "Stage Receptacle"
| 4 || 12
| 15A lights in large basement meeting room & rear basement hallway
|-
| 20A "Ball"room Furnace
| 3 || 11
| 15A "Office lights"
|-
| 15A Entrance Hall<br/>"Lower Bar Furnace"
| 2 || 10
| 15A basement flourescent "Lights"
|-
| 30A kitchen outlets, fridges "Refrigerator"
| 1 || 9
| 15A basement flourescent "Lights"
|} <br clear=all>
 
===Panel AD===
[[File:Panel-ad-new.jpeg|right|thumb|100px|Panel AD]]
 
Located upstage left (facing the ballroom) in North corner of West wall of stage
 
{| class="wikitable" style="text-align: center;"
|-
! Breaker # !! Label
|-
| 1 || GFI outlet (used for<br/>screen printing sink in<br/>Mezzanine Shower Room)
|-
|rowspan="2"| 2
| Vanity lights above stage
|-
| Stage Left Ballroom Floor Outlets
|-
|rowspan="2"| 3
| Upstage Center outlet<br />
& Stage Left Outlet
|-
| SE Ballroom (Library) Bathroom Lights<br />
& Exit Light
|-
| 4 || Stage Right Ballroom Floor Outlets<br />
& Stage Right Outlets
|-
| 5 || NW Ballroom (piano) Bathroom Light<br />
& NW Bathroom Hallway Light
|-
| 6 || Crow's Nest Interior light/fan<br />
& SW Ballroom Staircase Light<br />
& Ballroom Mop Closet Light<br />
& Lights beneath Ballroom Mezzanine<br />
& AV Room Lights
|} <br clear=all>
 
===Panel AE===
[[File:Panel-ae.jpg|right|thumb|Panel AE]]
 
This panel is no longer FPE and the info/picture needs to be updated
 
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| Stage left floor outlet/s
| 1 || 2 || Ballroom Under Bar<br/> Outlet #2 (from L)
|-
| Stage right floor outlet/s
| 3 || 4 || Ballroom Under Bar<br/> Outlet #1 (from L)<br/> Ballroom Shattuck Entrance's Exit Signs (3)
|-
| Ballroom Under Bar<br/> Outlet #3 (from L) || 5 || 6 || Stage Storage Room (office #3) Outlets
|-
| Ballroom Under Bar<br/> Outlet #4 (from L) || 7 || 8 || X
|-
| Ballroom Balcony S Wall Lights<br/> & SW Staircase Exit Signs<br/> & SE Staircase lights / exit signs<br/> & SW Ballroom wall outlets || 9 || 10 || X
|-
| X || 11 || 12 || X
|} <br clear=all>
 
===Panel B===
[[File:Panel-b.jpg|right|thumb|Panel B]]
 
100amps
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| X || 1 || 2 || X
|-
| X || 3 || 4 || X
|-
| X || 5 || 6
|rowspan="2"| Basement Vent
|-
| X || 7 || 8
|-
|rowspan="2"| [[Panel BA]]<br/>(Ballroom Balcony)
|| 9 || 10
|rowspan="2"| Sudo Equipment
|-
|| 11 || 12
|-
| Sudo Room Servers || 13 || 14 || X
|-
| Outlets in Room adjacent<br/>to Crow's Nest || 15 || 16 || X
|-
| X || 17 || 18 || Exhaust Fans & Outlets in<br/>over-stage Crow's Nest
|-
| X || 19 || 20 || Sudo Room outlets<br/>on South Wall
|} <br clear=all>
 
===Panel BA===
[[File:Panel-ba.jpg|right|thumb|Panel BA]]
 
'''''This panel is Federal Electric and needs to be replaced ASAP.'''''
 
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| Ballroom Fans || 1 || 2 || Balcony Chandelier (Single)
|-
| Ballroom Rafter/Lattice<br/> Disco Ball || 3 || 4
|rowspan="2"|Ballroom Chandeliers
|-
| X || 5 || 6
|-
| Aux #4 || 7 || 8
|rowspan="2"| [[#Panel BAAA|Panel BAAA]] (in entrance hall)
|-
| X || 9 || 10
|-
| Ballroom Rafter/Lattice<br/>Disco Ball Lights|| 11 || 12 || X
|-
| Aux #1 || 13 || 14 || Aux #2
|-
| Aux #5 || 15 || 16 || Aux #3
|} <br clear=all>
 
===Panel BAAA===
[[File:Panel-baaa.jpg|right|thumb|Panel BAAA]]
{| class="wikitable" style="text-align: center;"
|-
! Label -> !! Breaker # !! Breaker # !! <- Label
|-
| n/a || 2 || 1
|rowspan="2"| Outlet under counter<br/>(circuit 5 breaker nfg)
|-
| n/a || 4 || 3
|-
|rowspan="2"| Outlet (twist lock)<br/> on counter
| 6 || 5 || Outlet Under Counter
|-
| 8 || 7 || Outlet next to Counter<br/>(1ft above floor)<br/>& Outlet under counter
|} <br clear=all>
 
This panel used to be under the entrance hall bar counter. When that counter was demolished, this panel was moved to the wall.
 
===Panel C===
100amps
 
I couldn't find this panel to take a picture --yar
 
===Panel D===
 
[[File:Panel-D-2021-04-29.jpeg|left|thumb|Panel D]]
 
100 amps <br clear=all>
 
There is a wire in this box that comes from the other side of the wall, in a junction box 5' off the ground covered with a [https://www.google.com/search?q=2+gang+Plastic+Blank+Wall+Plate| 2 gang Plastic Blank Wall Plate] which is joined to wires assumed to go to outlets lower on that wall.  But since we didn't see the expected result when we hooked it up, it's not connected right now.  Also there are no available circuits left in this box.  That wire is labeled inside this panel.
 
[[Category:Building]]

Latest revision as of 01:34, 2 August 2021

This page provides a "living document" of the Omni Commons electrical system. It is not necessarily completely accurate, though it strives to be, and is always important to get updated! Also see our power usage, floorplans, old breaker diagram, and cancelled panels.

3 of these panels are Federal Pacific Electric and need to be replaced ASAP: A, AB, BA

  • Main Panel (in ANV office, room E of rear [48th St] exit)
    • Panel A (adjacent to main in ANV office)
      • Panel AB (in basement next to N staircase)
      • Panel AD (located upstage left in N corner of W wall of ballroom)
      • Panel AE (located in storage room S of stage in N corner of W wall of ballroom)
    • Panel B (in Crow's Nest above stage in ballroom)
      • Panel BA (in rear ballroom balcony near S wall)
          • Panel BAAA (behind Entrance Hall counter on S wall)
    • Panel C (in Disco Room at base of ladder to DJ booth)
    • Panel D (in ANV office on E wall shared with Entrance Hall)
  • CCL Panel - (Located next to door into CCL / sudo room area) - Apparently not yet documented here?


Main Panel

Omni's main electrical panel
Label -> Breaker # Breaker # <- Label
Panel B & Panel D 200amps 1 2
3 4
Panel A 200amps 5 6
7 8
X 9 10 Panel C 100amps
11 12
Storage #5 / Trash Room 13 14 n/a
15 16 n/a
Storage #5 / Trash Room 17 18 n/a
Counter Culture Labs
(CCL) Closet
19 20 n/a
21 22 n/a
n/a 23 24 n/a


Panel A

Panel A
Panel A open

This panel is Federal Electric and needs to be replaced ASAP.

200amps

Label -> Breaker # Breaker # <- Label
1 21 Panel AE
2 22
Panel AB 3 23
4 24
Panel AC (breaker is removed until kitchen renovated) 5 25 Panel AD
6 26
7 27
8 28
9 29  
Upstairs (cafe mezzanine) kitchen light /
Upstairs (cafe mezzanine) bathroom lights /
Exit Sign at top of W cafe mezzanine staircase
10 30 Sudo Room outlets
on South Wall
Outlets along north wall of entrance hall 11 31
Hood over oven in upstairs
kitchenette (cafe mezzanine) /
W Wall Kitchenette Outlet (R of sink) /
W wall kichenette outlet (Above oven in alcove)
12 32
CCL storage rooms lights 13 33
14 34
switch on wall of disco room 15 35
16 36 X
Right switch disco room fans 17 37 Blue Classroom S wall outlets
2 TIL Office Lights (upstairs) /
Front Door Exit Sign /
Two Lights on Beam at entrance
18 38
Light fixture and outlets in
Blue Classroom alcove on N wall
19 39
Upstairs kitchenette (cafe mezzanine) S wall outlets /
W Wall Kitchenette Outlet (L of sink) /
N wall kitchenette outlets (at entrance) /
Outlets under bar on S Wall of Disco Room
near S Wal of Kitchenette
20 40


Panel AB

Panel AB

This panel is Federal Electric and needs to be replaced ASAP.

In 2019 we added another circuit to this box to power lights & outlets in the secure storage closet above it. In the confusion, something may have been switched around. Liblens briefly lost power. Needs to be re-assessed and re-labeled.
"quotes" are from old breaker diagram re: "DOWNSTAIRS DINING AREA PANEL"

7/8 is one breaker, see image.

Label -> Breaker # Breaker # <- Label
20A basement furnace? "Blank" 8 16 15A "Blank" (nothing connected)
"Dining Room Furnace" 7 15 15A Liberated Lens, other small basement rooms & adjacent outlets.
15A pantry & "Kitchen Lights" 6 14 15A
20A 5 13 15A large basement meeting room - most outlets except on south wall "Receptacle"
20A "Stage Receptacle" 4 12 15A lights in large basement meeting room & rear basement hallway
20A "Ball"room Furnace 3 11 15A "Office lights"
15A Entrance Hall
"Lower Bar Furnace"
2 10 15A basement flourescent "Lights"
30A kitchen outlets, fridges "Refrigerator" 1 9 15A basement flourescent "Lights"


Panel AD

Panel AD

Located upstage left (facing the ballroom) in North corner of West wall of stage

Breaker # Label
1 GFI outlet (used for
screen printing sink in
Mezzanine Shower Room)
2 Vanity lights above stage
Stage Left Ballroom Floor Outlets
3 Upstage Center outlet

& Stage Left Outlet

SE Ballroom (Library) Bathroom Lights

& Exit Light

4 Stage Right Ballroom Floor Outlets

& Stage Right Outlets

5 NW Ballroom (piano) Bathroom Light

& NW Bathroom Hallway Light

6 Crow's Nest Interior light/fan

& SW Ballroom Staircase Light
& Ballroom Mop Closet Light
& Lights beneath Ballroom Mezzanine
& AV Room Lights


Panel AE

Panel AE

This panel is no longer FPE and the info/picture needs to be updated

Label -> Breaker # Breaker # <- Label
Stage left floor outlet/s 1 2 Ballroom Under Bar
Outlet #2 (from L)
Stage right floor outlet/s 3 4 Ballroom Under Bar
Outlet #1 (from L)
Ballroom Shattuck Entrance's Exit Signs (3)
Ballroom Under Bar
Outlet #3 (from L)
5 6 Stage Storage Room (office #3) Outlets
Ballroom Under Bar
Outlet #4 (from L)
7 8 X
Ballroom Balcony S Wall Lights
& SW Staircase Exit Signs
& SE Staircase lights / exit signs
& SW Ballroom wall outlets
9 10 X
X 11 12 X


Panel B

Panel B

100amps

Label -> Breaker # Breaker # <- Label
X 1 2 X
X 3 4 X
X 5 6 Basement Vent
X 7 8
Panel BA
(Ballroom Balcony)
9 10 Sudo Equipment
11 12
Sudo Room Servers 13 14 X
Outlets in Room adjacent
to Crow's Nest
15 16 X
X 17 18 Exhaust Fans & Outlets in
over-stage Crow's Nest
X 19 20 Sudo Room outlets
on South Wall


Panel BA

Panel BA

This panel is Federal Electric and needs to be replaced ASAP.

Label -> Breaker # Breaker # <- Label
Ballroom Fans 1 2 Balcony Chandelier (Single)
Ballroom Rafter/Lattice
Disco Ball
3 4 Ballroom Chandeliers
X 5 6
Aux #4 7 8 Panel BAAA (in entrance hall)
X 9 10
Ballroom Rafter/Lattice
Disco Ball Lights
11 12 X
Aux #1 13 14 Aux #2
Aux #5 15 16 Aux #3


Panel BAAA

Panel BAAA
Label -> Breaker # Breaker # <- Label
n/a 2 1 Outlet under counter
(circuit 5 breaker nfg)
n/a 4 3
Outlet (twist lock)
on counter
6 5 Outlet Under Counter
8 7 Outlet next to Counter
(1ft above floor)
& Outlet under counter


This panel used to be under the entrance hall bar counter. When that counter was demolished, this panel was moved to the wall.

Panel C

100amps

I couldn't find this panel to take a picture --yar

Panel D

Panel D

100 amps

There is a wire in this box that comes from the other side of the wall, in a junction box 5' off the ground covered with a 2 gang Plastic Blank Wall Plate which is joined to wires assumed to go to outlets lower on that wall. But since we didn't see the expected result when we hooked it up, it's not connected right now. Also there are no available circuits left in this box. That wire is labeled inside this panel.